Detailed Specification



S. No.
PARAMETERS
UNITS
BEFORE FILTRATION
AFTER FILTRATION
1
Break Down Voltage with 2.5mm Electrode Gap. kV 25 >50- 70
2
Moisture Removal ppm 50-100 Up to < 5 - 10
3
Neutralization Value (With IRC Option Only) mg of KOH/g 0.5 < 0.1
4
Particle size (Filter Fineness) Micron Visible < 1
5
Gas Content % Vol./Vol. <10% < 0.1%